Duct Air Quality (VOC) transmitter VOCD-series

Description

Duct Air Quality (VOC) transmitter VOCD-series
The Duct Air Quality (VOC) transmitter VOCD-series have
MEMS type MOX sensing element

Output(s) for Duct Air Quality (VOC) transmitter VOCD-series are
0-10 Vdc, 2-10 Vdc, 4-20 ma, 0-5 Vdc or 1-5 Vdc
(One output and Two VOC outputs available).

Estimated operating life for
Duct Air Quality (VOC) transmitter VOCD-series is minimum 5 years.

Accuracy for Duct Air Quality (VOC) transmitter VOCD-series is +/-10% FSO.

Power supply for Duct Air Quality (VOC) transmitter VOCD-series is 24 Vac/dc.

  • "Options"

    • Modbus RS485
    • LCD Display
    • 1 x relay output , can be set individually
    • 2 x relay outputs , can be set individually
    • Buzzer
  • VOC Ranges/Sensitivity

    0V or 4mA:  BEST, Clean Air
    1V or 5.6mA:  STANDARD, calibrated level, reference level
    10V or 20mA:  WORST, polluted air

    In normal conditions, base level is equals to 1V.

    Lower than 1V is better than calibrated situation.
    In some cases, indoor condition may be better than calibrated level.

    Higher than 1V is showing polluted air level.
    Pollution is measured from 1V to 10V.

    Sensitivity for VOC.
    Higher response for VOC gasses at HIGH sensitivity.
    10V of HIGH is equal to 4V of LOW.
    10V of MEDIUM is equal to 6V of LOW.
    1V is same for all sensitivities.
    Example:  3.0V @ LOW  ==  4.6V @ MEDIUM  ==  7.0V @ HIGH

  • Detectable gases

    • Cigarette smoke
    • Automobile exhaust
    • Breath air
    • Carbon monoxide (CO)
    • Solvent fumes • Alcohol fumes
    • Acetone
    • Acrylonitrile
    • Ammonia
    • Benzene
    • Chlorine
    • Dimethyl amine
    • Ethane
    • Ethanol
    • Ethylene
    • Ethylene oxide
    • Formaldehyde
    • Hydrogen
    • Hydrogen sulfide
    • Isobutane
    • Methane
    • Methanol
    • n-Hexane 2
    • n-Petane
    • Propane
    • Sulfur dioxide

  • Ordering examples

    VOCD 51
    Duct Air Quality (VOC) transmitter
    VOC output 1: 4-20 mA
    VOC output 2: 0-10 Vdc

    VOCD 51 M
    Duct Air Quality (VOC) transmitter
    VOC output 1: 4-20 mA
    VOC output 2: 0-10 Vdc
    Modbus RS485 communication

    VOCD 51 MDR2B
    Duct Air Quality (VOC) transmitter
    VOC output 1: 4-20 mA
    VOC output 2: 0-10 Vdc
    Modbus RS485 communication, LCD Display, 2 x relay outputs and Buzzer.

    See data sheet for wide range of different combinations.

Download

Please enable JavaScript in your browser to complete this form.

Send us Your inquiry in contact form below.

Copyright 2025 © All rights Reserved. Hemsida Webbdesign Interwebsite Webbyrå