- Ranges:
• RNO2 20 with range 0-20 ppm
• RNO2 100 with range 0-100 ppm
-
- IP65 protection for both enclosure and sensor
- Outputs
• 2 x 4-20 mA or 0-10 Vdc, user settable
• RS485, Modbus RTU protocol
-
- Power supply
• 24 Vdc
• 24 Vac as option
- Electrochemical sensor
Description for
Nitrogen Dioxide (NO2) Gas Detector RNO2-series
Nitrogen Dioxide (NO2) Gas Detector RNO2-series is intended
for Nitrogen Dioxide (NO2) measurement of vehicle exhaust
(from running diesel engines) measuring at garages, auto parks, road tunnels etc.
Nitrogen Dioxide (NO2) Gas Detector RNO2-series have replaceable Electrochemical Cell (sensor).
Measuring ranges for Nitrogen Dioxide (NO2) Gas Detector RNO2-series is
0-20 ppm or 0-100 ppm.
Nitrogen Dioxide (NO2) Gas Detector RNO2-series have
analog outputs 2 x 0-10 Vdc 4-20 mA (user settable) and
RS485, Modbus RTU protocol.
Response time t90 for Nitrogen Dioxide (NO2) Gas Detector
RNO2 20 (0-20 ppm) is <40 seconds and
<60 seconds for RNO2 100 (0-100 ppm)
Power supply for Nitrogen Dioxide (NO2) Gas Detector RNO2-series is 24 Vdc,
24 Vac is optionional.
Nitrogen Dioxide (NO2) Gas Detector RNO2-series enlosure is IP65.
The electrochemical cell (sensor) have microporous PTFE dust filter to ensure IP65 also for the electrochemical cell (sensor).
Nitrogen Dioxide (NO2) Gas Detector RNO2-series have 2 years expected sensor life time.
Nitrogen Dioxide (NO2) Gas Detector RNO2 can be supplied with a remote LCD display, wall mount enclosure with 3 meter cable as option.